Unit type data | |||||||||||
Fuel type |
Natural gas |
||||||||||
Equipment type |
1000NGS/1000NG |
||||||||||
Assembly |
Power supply + Heat exchange system + The fume recovery steam boiler |
||||||||||
Continuous output | |||||||||||
Fuel type |
Natural gas |
||||||||||
power modulation |
50% |
75% |
100% |
||||||||
Electrical output | kW |
600 440 295 224 1505 |
900 635 455 350 2215 |
1000 840 645 479 2860 |
|||||||
Coolant heat [1] | kW | ||||||||||
Exhaust gas heat (at 120 ℃) | kW | ||||||||||
Steam boiler heat output(max.)[2] | kW | ||||||||||
Energy input | kW |
Efficiency in mains parallel mode | |||||||||||
Electrical efficiency | % |
33.4 29.2 14.8 77.4 |
34.5 28.6 15.8 78.9 |
35.1 29.3 16.7 81.1 |
|||||||
Coolant Heat efficiency (max.) | % | ||||||||||
Steam boiler efficiency (max.)[2] | % | ||||||||||
Overall efficiency | % | ||||||||||
Steam boiler | |||||||||||
Inlet temperature | Water or Steam | ℃ |
143 |
||||||||
Inlet pressure | Absolute pressure | Mpa |
0.4 |
||||||||
Working temperature | Steam | ℃ |
151 |
||||||||
Working pressure | Absolute pressure | Mpa |
0.51 |
||||||||
Rated evaporation(Inlet medium steam) | Standard / Max. | kg/h |
53999~115510[2] |
||||||||
Rated evaporation(Inlet medium water) | Standard / Max. | kg/h |
373~1798[3] |
||||||||
Thermal efficiency |
% |
16.7 |
|||||||||
Fume inlet temperature | Max. | ℃ |
520 |
||||||||
Fume outlet temperature | Min. | ℃ |
210 |
||||||||
Fume recovery standard temperature difference | return/forward |
K |
310 |
||||||||
Working medium | standard |
|
Water / Steam |
||||||||
Coolant filling quantity | Water / Max |
L |
1000 |
||||||||
Min. boiler coolant circulation quantity | Water | kg/h |
100 |
||||||||
Highest pressure | Mpa |
1.25 |
|||||||||
Highest temperature | ℃ |
250 |
Gas Data | |||
Fuel |
[3] Natural gas |
||
Gas intake pressure |
3.5Kpa~50Kpa & ≥4.5bar |
||
Methane volume content |
≥ 80% |
||
Low heat value(LHV) |
Hu ≥ 31.4MJ/Nm3 |
||
Gas Consumption per hour at 50% load at 75% load at 100% load |
155 m3 225 m3 300 m3 |
||
[3] The relevant data of the technical manual will be revised after the natural gas components being supplied by User.Special statement:1、The technical data are based on natural gas with a calorific value of 10 kWh/Nm³ and a methane no. > 90%2、The technical data indicated is based on standard conditions according to ISO8528/1, ISO3046/1 and BS5514/13、The technical data is measured in standard conditions: Absolute atmospheric pressure:100kPa Ambient temperature:25°C Relative air humidity:30%4、Rating adaptation at ambient conditions according to DIN ISO 3046/1.The tolerance for the specific fuel consumption is + 5 % at rated output. | |||
Emission data[3] | |||
Exhaust flow rate ,moist [4] |
5190 kg/h |
||
Exhaust flow rate ,dry |
4152 Nm3/h |
||
Exhaust temperature |
220℃~210℃ |
||
Maximum allowable exhaust back pressure |
4.0Kpa |
||
Genset compliance with standard Emission: |
ISO3046,ISO8528,GB2820, CE,CSA,UL,CUL |
||
Standard |
SCR(Option) |
||
NOx, at 5% residual oxygen&100% load |
< 500 mg/Nm³ |
< 250 mg/Nm³ |
|
CO, at 5% residual oxygen&100% load |
≤ 600 mg/Nm3 |
≤ 300 mg/Nm3 |
|
Environmental noise | |||
Sound pressure level at a distance of up to 7 m(based on surroundings) | SA1000NG/89dB (A) & SA1000NGS/75dB (A) |
Prime power Operating Data Mode | ||||||
Synchronous alternator |
Star, 3P4h |
|||||
Frequency | Hz |
50 |
||||
Rating (F) KVA prime power | KVA |
1500 |
||||
Power factor |
0.8 |
|||||
Generator voltage | V |
380 |
400 |
415 |
440 |
|
Current | A |
2279 |
2165 |
2086 |
1968 |
Scope of Supply | ||||
Engine | Alternator Canopy and base Electrical cabinet | |||
Gas engine Ignition system Lambda controllerElectronic governor actuatorElectrical start motorBattery system | AC alternatorH class insulationIP55 protectionAVR voltage regulatorPF control | Steel sheel base frameEngine bracket Vibration isolators Soundproof canopy (optional)Dust filtration (optional) | Air circuit breaker7-inch touch screenCommunication interfaces Electrical switch cabinetAuto charging system | |
Gas supply system | Lubrication system | Standard voltage | Induction/exhaust system | |
Gas safety trainGas leakage protectionAir/fuel mixer | Oil filterDaily auxiliary oil tank (optional)Auto refilling oil system | 380/220V400/230V415/240V | Air filterExhaust silencerExhaust bellows | |
Gas Train | Service and documents | |||
Manual cut-off valve2~7kPa pressure gaugeGas filterSafety Solenoid valve (anti-explosion type is optional) pressure regulatorFlame arrestor as option | Tools package Engine operation Installation and operation manual Gas quality specification Maintenance manual Control system manual Software manual After service guide Parts manual Standard package | |||
Optional configuration |
Engine | Alternator | Lubrication system |
Coarse air filterBackfire safety control valveWater heater | Generator Brand: Stamford, Leroy-Somer,MECCTreatments against humidity and corrosion | Brand new oil tank with large capacityOil consumption measuring gaugeFuel pumpOil heater |
Electrical system | Gas supply system | Voltage |
Remote monitoring Grid-connection remote control sensor | Gas flow gaugeGas filtrationPressure reducer gas pretreatment alarm system | 220V230V240V |
Service and documents | Exhaust system | Heat exchange system |
Service toolsMaintenance and service parts | Three-way catalytic converterGuard shield from touchResidential silencerExhaust gas treatment | Emergency radiatorElectric heaterHeat recovery systemThermal storage tank |
Main functions | |||||
Engine running timeAlarm Protection Function
|
12V or 24V DC StartingRemote Control Interface as an optionAutomatic Start/Stop Control SwitchSet Input, Output, Alarm and TimeNumbers Control Input, Relays Control OutputAutomatic failure state emergency stop and fault display battery voltage genset frequencyProtection with IP44Gas leaking detection | ||||
Standard configuration | |||||
Engine Control: Lambda closed loop controlIgnition systemElectronic governor actuatorStart up control speed control load control | Generator Control:Power control RPM control (synchronous) Load distribution (island mode) Voltage control | Voltage tracking (synchronous) Voltage control (island mode)Reactive power distribution(island mode) | Other controls: Oil filling automaticallyIntake Valve controlFan control | ||
Early warning monitoring | |||||
battery voltageAlternator data:U、I、Hz、kW、 kVA、kVAr、PF、kWh、kVAhGenset frequency | Engine SpeedEngine running timeInlet pressure temperatureOil pressure | Coolant temperatureMeasurement of oxygen content in exhaust gasIgnition status inspection | Coolant temperatureFuel gas inlet pressure | ||
Protection functions | |||||
Engine protection Low oil pressureSpeed protectionOver speed/short speedStarting failureSpeed signal lost | Alternator protection
|
Busbar/mains protection
|
System protection Alarm Protection FunctionHigh coolant temperatureCharge faultEmergency Stop |
Genset size (length * width * height) mm | 12192×2435×5500(Container) |
Genset dry weight(Open Type) kg | 22000(Container |
Spraying Process | High quality powder coating(RAL 9016)) |